The lab
Break things in a simplified teaching model of an example hall: 16 racks at 150 kW (2.4 MW of IT load), four power paths and four cooling trains. Pick a scenario or click any part to fail it, then watch what the backup does.
Teaching model Simplified physics with assumed values. It is not a design tool, a digital twin or an availability promise; a real site needs its own engineering studies.
- Live paths
- 4 / 4 8 of 8 rack feeds
- Power per rack
- 150 kW 150 kW asked for
- Available compute
- 100% 2.40 MW block load
- Simulated time
- 00:00 1× speed
At 150 kW, three paths carry the full load. With two paths left, each rack gets at most 132 kW.
The clock pauses when the simulator is off screen.
What happened
- All four paths are live. Pick a scenario to follow a transfer.
Assumptions: 16 racks, two 33 kW power shelves per path per rack, four independent paths, a 10 s generator start and 10 minutes of battery at full path load. Battery time stretches at lower load. Losing two paths caps rack power.
- Available compute
- 100% thermal limit
- Coolant to racks
- 35.0 °C limit starts at 40 °C
- Rack pressure difference
- 1.20 bar minimum 1.0 bar
- Liquid-cooled heat
- 1.92 MW 00:00
Above 28 °C the dry coolers use adiabatic pre-cooling.
The clock pauses when the simulator is off screen.
What happened
- Cooling at the design point. All trains running.
Assumptions: 1.92 MW of liquid-cooled heat at 100% load, four CDUs, four facility pumps and four dry coolers on shared headers, 25 °C outdoor design point, 35 °C coolant to the racks and 1.2 bar across them. Values move with first-order lags, so changes take seconds to settle.
See parts like these in 3D on the anatomy page. For how designers check the air in a data hall, see how cooling is studied.
Adapted from the resilience tools on Eliovp's ModFlex engineering page.